Herunterladen Inhalt Inhalt Diese Seite drucken

Test Procedure; Functional Test - Dehn PHE III Gebrauchsanleitung

Spannungsprüfer
Vorschau ausblenden Andere Handbücher für PHE III:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

6.

Test procedure

Testing is only allowed if the "Notes on safe operation" of the relevant PHE3... voltage detector are
observed (see chapter 5, page 8).
6.1 Functuional test
A functional test must be performed before verifying absence of supply voltage.
When pressing the "TEST" button for about 3 seconds; see Fig. 6.1), the indicator is switched on and is
checked for proper operation.
When pressing the "TEST" button, the red indicator light is flashing and an intermittent acoustic signal
sounds, when releasing the "TEST" button, the green indicator light is permanently illuminated. The
PHE3... voltage detector is operational for approximately 90 to 120 sec.
If both indicator lights are permanently illuminated and a continuous acoustic signal sounds when releasing the
"TEST" button, the battery is low. The voltage detector is no longer operational. Insert a new battery (see
Fig. 6.1, Table 6.1 and Fig. 9.3 on page 14). Now repeat the functional test. If the indication signals described
above still do not appear, immediately remove the PHE3... voltage detector from service and return it to
DEHN + SÖHNE for repair.
G
Green indicator light
R
Red indicator light
T
"TEST" button
A
Outlet for acoustic signal
Fig. 6.1 Indication signals
Permanent green indicator light
Flashing red indicator light and
intermittent acoustic signal
Green and red indicator light are
illuminated at the same time and a
continuous acoustic signal sounds
Table 6.1
10
Voltage states are visually (indicator group I) and acoustically (indicator group III) indicated
Indication
No indicator light
Meaning of the indication signals
Note:
The indication of the PHE3... voltage
detector is only clear if one of the two
indicator lights is illuminated or the red
indicator light is illuminated and an
intermittent acountec signal sounds.
A G T R
Voltage / operating state
No voltage present
Voltage present
Functional test (see 6.1)
(replace battery according to 9.3,
not performed
Low battery
page14)

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis