ELECTRICAL WIRING
10.3 COMMON WIRING
!
C A U T I O N
All the field wiring and electrical components must comply with local codes.
10.3.1 Electrical wiring between indoor unit and outdoor unit
Connect the electrical wires between the indoor unit and the
outdoor unit, as shown below.
Follow local codes and regulations when performing
electrical wiring.
If the refrigerant piping and the control wiring are connected
to the units in the same refrigerant cycle.
Use twist pair wire (more than 0.75 mm²) for operation wiring
between outdoor unit and indoor unit, and operation wiring
between indoor unit and indoor unit.
Use 2-core wire for the operating line (Do not use wire with
more than 3 cores).
Use shielded wires for intermediate wiring to protect the
units from noise obstacle at length of less than 300 m and
size complied with local code.
Power source from the outdoor unit to the indoor unit
Nº 0 System
Outdoor unit
Indoor Unit
Terminal board
Circuit Breaker
Earthleakage Breaker
Field Wiring
Field supplied
Optional Accessory
15
PMML0396B rev.0 - 11/2015
Operating Line (Twisted
Shielded Pair Cable or
Shielded Pair Cable)
DC5V (Non-Pole
Transmission)
Indoor Unit
Remote
Control
Switch
Max. 3 Units per Refrigerant Cycle
Open a hole near the connection hole of power source
wiring when multiple outdoor units are connected from one
power source line.
The recommended breaker sizes are shown in Table of
electrical data and recommended Wiring, Breaker Size/1
O.U.
In the case that a conduit tube for field-wiring is not used, fix
rubber bushes with adhesive on the panel.
All the field wiring and equipment must comply with local and
international codes.
H-LINK twist pair shielded cable must be grounded in the
outdoor unit side.
!
C A U T I O N
Pay attention to the connection of the operating line. Incorrect connection
may cause the failure of PCB.
Independent power source of outdoor unit and indoor unit
Nº 0 System
Outdoor unit
Operating Line
(Twisted Shielded Pair
Cable or Shielded Pair
Cable)
DC5V (Non-Pole
Transmission)
Indoor Unit
Indoor Unit
Remote
Control
Switch
Max. 3 Units per Refrigerant Cycle