UNITS INSTALLATION
100 mm or more of the side space is acceptable on the
Upper Side
Blocked
The length A is as shown in the following table:
Upper Side Open
Be sure to use the fan direction guide. Leave open both right
The length A is as shown
in the following table:
When L > H, use a base for outdoor unit to make L ≤ H.
Close the base not to allow the outlet air bypassed.
6
PMML0396B rev.0 - 11/2015
service cover side.
Be sure to use the fan direction guide.
Leave open both right and left sides.
L
A
600 or greater
0<
L
≦
1/2H
1200 or greater
1/2H
<
L
≦
H
Outlet Side Blocked
Single Installation
and left sides.
L
0<L≤1/2H
1/2H<L≤H
Allow 100 mm of space between units. Leave open both right
Be sure to use the fan direction guide. Allow 100 mm of
space between units. Leave open both right and left sides.
Serial installation allowed up to two units.
Be sure to use the fan direction guide. Allow 100 mm of
space between units. Leave open both right and left sides.
Serial installation allowed up to two units.
Multiple Installation (Two units or more)
Allow 100mm of space between units. Both right and left
Be sure to use the fan direction guide. Allow 100 mm of
space between units. Serial installation allowed up to two
units. Leave open both right and left sides.
The length A is as shown
A
in the following table:
≥200
≥300
When L > H, use a base for outdoor unit to make L ≤ H.
Close the base not to allow the outlet air bypassed.
and left sides.
sides shall be open.
L
0<L≤1/2H
≥250
1/2H<L≤H
≥350
A