System Functions - Balluff BES M18EH1-L01C80B-S04G-L04 Konfigurationsanleitung

Vorschau ausblenden Andere Handbücher für BES M18EH1-L01C80B-S04G-L04:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

BES M08EH1-L01C20B-S04G-L04 /BES M12E_1-L01C_0_-S04G-L04 /
BES M18EH1-L01C_ _ _-S04G-L04
Inductive sensors
6

System functions

6.1
Device Status and Detailed Device Status
6.1.1
Description
The Device Status feature provides information about the
current device status.
Each Device Status is combined with a corresponding
diagnostic message (Events see chapter 3.6 on page
22).
It also gives the user the possibility to actively read out
currently pending events of the device.
6.1.2
Process Data
Also see section Process Data Profiles on page 9.
6.1.3
ISDU
Name
Device Status
Detailed Device Status
Detailed Device Status
Tab. 6-1:
Device status and detailed device status – ISDU
6.1.4
Device Status
The parameters are accessed via subindex 0. The output
values are to be interpreted as follows:
Value
Status
0
Device is operating properly.
1
Maintenance Required
2
Out-of-Specification
3
Functional check
4
Failure
Tab. 6-2:
Device Status
78
english
Index
Subindex
0x0024 (36)
0
0x0025 (37)
0
1...10
Access
Length
Data Type Data Storage
R
1 byte
UINT8
R
30 Byte
R
3 byte
RECORD
Description
Device working correctly.
Although the process data is valid, internal diagnoses show that
the device will soon lose its ability to function properly.
Maintenance is necessary.
Although the process data is valid, internal diagnoses show that
the device is operating outside of its specified measurement
range or environmental conditions. The installation must be
checked for unintentional malfunctions.
Process data is temporarily invalid due to intentional changes to
the device, e.g., parameterization or teaching-in.
Process data is invalid due to a malfunction of the device or its
peripheral devices. The device is not able to perform its
intended function. Re-configuration (resetting to factory settings)
can help. Otherwise, Balluff service must be contacted or the
device replaced.
Default
n/a
n/a
n/a
0x00 0x00
0x00