Herunterladen Inhalt Inhalt Diese Seite drucken

Electrical Connections To The Electric Pump Mce-22/P - Mce-15/P - Mce-11/P; Figure 4: Pump Connection Mce 22/P - Mce 15/P - Mce 11/P - DAB MCE-150/P Installations- Und Wartungsanleitungen

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 192
2.2.1.4
Electrical connections to the electric pump MCE-22/P – MCE-15/P – MCE-11/P
Models MCE 22/P – MCE 15/P – MCE 11/P require motor configuration for a three-phase voltage of 230V.
This is normally obtained by a delta configuration of the motor. See Figure 4.
Incorrect connection of the earthing line, to a terminal other than the earth terminal can cause
irremediable damage to the equipment.
Incorrect connection of the power line on the output load terminals can cause irremediable
damage to the equipment.
10 m
20 m
30 m
1,5
1,5
1,5
4 A
1,5
1,5
1,5
8 A
1,5
1,5
2,5
12 A
2,5
2,5
2,5
16 A
2,5
2,5
20 A
4
4
24 A
6
6
28 A
6
6
32 A
10
10
36 A
10
10
40 A
10
10
44 A
10
10
48 A
16
16
52 A
16
16
56 A
16
16
60 A
As regards the section of the earthing cable, refer to current standards.
Figure 6: Pump connection MCE 22/P – MCE 15/P – MCE 11/P
Cable section in mm²
40 m
50 m
60 m
1,5
1,5
1,5
1,5
2,5
2,5
2,5
4
4
4
4
4
6
4
6
6
10
6
6
10
10
6
6
10
10
10
10
10
10
10
10
10
16
10
10
10
16
10
10
16
16
16
16
16
16
16
16
16
16
16
16
16
16
Table applicable to cables in PVC with 4 wires (3 phases + earth)
Table 6: Section of 4-wire cable (3 phases + earth)
ENGLISH
70 m
80 m
90 m
1,5
1,5
2,5
2,5
4
4
4
6
6
6
6
10
6
10
10
10
10
10
10
10
10
16
10
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
77
100 m
120 m
140 m
2,5
2,5
2,5
4
4
6
6
6
10
10
10
10
10
10
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
160 m
180 m
200 m
4
4
4
6
6
10
10
10
10
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis