If the inverter is configured as reserve, the upper section of the icon representing the motor is displayed in
colour, while the display remains the same as in Table 15 with the exception that if the motor is stationary F
is displayed instead of Sb.
If one or more inverters have RC without a setting, the letter A appears in place of the status information
(below all icons of the inverters present), and system start-up is disabled.
To reserve more space for the system display, the name of the parameter SM is not shown, but
simply the text "system" below the menu name
6.1.6

VE: Display of version

Hardware and software version of the equipment.
For firmware versions 26.1.0 and later, the following also applies:
On this page after the prefix S: the last 5 figures of the single serial number attributed for connectivity are
showed. The whole serial number can be viewed by pressing the "+" key

6.2 Monitor menu

The MONITOR MENU is accessed from the main menu by pressing and holding the buttons "SET" and "-"
(minus) simultaneously for 2 seconds, or via the selection menu using buttons + or -.
Within this menu, by pressing MODE, the following values are displayed consecutively.
6.2.1

VF: Flow display

This displays the instant flow in [litres/min] or [gal/min] depending on the set unit of measurement. If the mode
without flow sensor is selected, an adimensional flow is displayed.
6.2.2

TE: Display of final power stage temperature

6.2.3

BT: Display of electronic board temperature

6.2.4

FF: Display of fault log

Chronological display of faults occurring during system operation.
Tow numbers x/y are displayed below the symbol FF, which indicate respectively "x" for the fault displayed
and "y" for the total number of faults present; an indication of the type of fault is displayed to the right.
Buttons + and – can be used to scroll through the list of faults: press – to move back through the log through
to the oldest fault present, or + to scroll forward to the most recent.
The faults are shown in chronological order, starting from the oldest x=1 to the most recent x=y. The maximum
number of faults displayable is 64; after which the system overwrites the oldest versions in order.
This menu item displays the fault list but does not enable reset. The list can only be cleared by means of the
specific command in the item RF of the TECHNICAL ASSISTANCE MENU.
Neither a manual reset or shutdown of the unit, or restored default settings will clear the fault log; only the
above procedure will enable this.
6.2.5

CT: Display contrast

This adjusts the display contrast.