3. APPLICATIONS
The inverter of the MCE/C series is a device conceived for the management of circulation pumps allowing
integrated regulation of the differential pressure (head); it is thus possible to adapt the performance of the
circulation pump to the actual demands of the system.
This determines considerable energy saving, a greater possibility of control of the system, and reduced
noise.
The MCE-55/C inverter is designed so that it can be housed directly on the pump motor body.

4. TECHNICAL DATA

Inverter power
supply
Inverter output
Mechanical
characteristics
Installation
Hydraulic
characteristics
of regulation
and operation
Sensors
Functionality
and
protections
Temperatures
Table 1: Technical data
4.1

Electromagnetic Compatibility (EMC)

MCE inverters respect standard EN 61800-3, in the C2 category, for electromagnetic compatibility.
-
Electromagnetic emissions. Residential environment (in some cases restrictive measures may be
requested).
-
Conducted emissions. Residential environment (in some cases restrictive measures may be
requested).
Voltage [VAC]
(Tol. +10/-20%)
Phases
Frequency [Hz]
Current [A]
Voltage [VAC]
Phases
Frequency [Hz]
Current [A rms]
Mechanical power P2
Weight of unit [kg]
(control unit only, excluding package)
Max. dimensions [mm]
(LxHxD)
Work position
Grade of protection IP
Max. ambient temperature [°C]
Differential pressure regulating
range
Type of pressure sensors
Differential pressure sensors full
scale value [bar]
Connectivity
Protections
Storage temperature [ºC]
ENGLISH
MCE-55/C
380-480
3
50/60
17,0-13,0
0 - V supply
3
0-200
13,5
7.5 HP / 5,5 kW
housed on the pump motor body
1 - 95% full scale pressure sensor
Multi inverter connection
Self protected against overload
Excess temperature of internal
electronics
Abnormal supply voltages
Direct short circuit between output
phases
37
MCE-30/C
380-480
3
50/60
11,5-9,0
0 - V supply
3
0-200
7,5
4.0 HP / 3 kW
7.6
270x355x195
55
40
Ratiometric
4/10
-10 ÷ 40