Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data - Victron energy Phoenix 12/1600 Anleitung

Vorschau ausblenden Andere Handbücher für Phoenix 12/1600:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 27

7. Technical data

Phoenix Inverter Smart
Parallel and 3-phase operation
Input voltage range (1)
Output
Cont. output power at 25ºC (2)
Cont. output power at 25ºC
Cont. output power at 40ºC
Cont. output power at 65ºC
Peak power
Dynamic (load dependent) DC
low shut down (fully
configurable)
Max. efficiency 12/ 24 /48 V
Zero load power 12 / 24 / 48 V
Zero load power in ECO mode
Programmable relay (2)
Stop & start power ECO-mode
Protection (3)
Bluetooth wireless
communication
VE.Direct communication port
Remote on-off
Common Characteristics
Common Characteristics
Battery-connection
230 V AC-connection
Weight
Dimensions (hxwhd)
Safety
Emission Immunity
Automotive Directive
1) Non-linear load, crest factor 3:1
2) Programmable relay that can a.o.
be set for general alarm, DC under
voltage or genset start/stop function.
AC rating: 230 V / 3 A
DC rating: 3 A up to 30 VDC, 0.2A
up to 70 VDC
8
12/1600
24/1600
48/1600
INVERTER
9,3 – 17V
Output voltage: 230VAC ±2% 50 Hz or 60Hz ± 0,1% (1)
1600 VA
1300 W
1200 W
800 W
3000 W
Dynamic cut-off, see
https://www.victronenergy.com/live/ve.direct:phoenix-inverters-dynamic-cutoff
92 / 94 / 94%
92 / 94 / 94%
8 / 9 / 11 W
0.6 / 1.3 / 2.1 W
0.6 / 1.3 / 2.1 W
GENERAL
For remote monitoring and system integration
For remote monitoring and system integration
Operating temperature range: -40 to +65ºC (fan assisted cooling)
Humidity (non-condensing): max 95%
ENCLOSURE
Material & Colour: steel (blue RAL 5012; and black RAL 9017)
M8 bolts
12kg
485 x 219 x 125mm
485 x 219 x 125mm
STANDARDS
EN 55014-1 / EN 55014-2 / EN-IEC 61000-6-1
EN-IEC 61000-6-2 / EN-IEC 61000-6-3
3) Protection key:
a) output short circuit
b) overload
c) battery voltage too high
d) battery voltage too low
e) temperature too high
f) 230 V AC on inverter output
g) input voltage ripple too high
12/2000
12/3000
24/2000
24/3000
48/2000
48/3000
No
18,6 – 34V
37,2 – 68V
2000 VA
3000 VA
1600 W
2400 W
1450 W
2200 W
1000 W
1700 W
4000 W
6000 W
93 / 94 / 95%
8 / 9 / 11 W
12 / 13 / 15 W
1.5 / 1.9 / 2.8 W
Yes
adjustable
a - g
Yes
Protection category: IP 21
12 V/24 V: 2+2 M8 bolts
M8 bolts
48 V: M8 bolts
Screw terminals
13kg
19kg
533 x 285 x 150mm (12 V)
485 x 285 x 150mm (24 V/48 V)
EN-IEC 60335-1
ECE R10-5
24/5000
48/5000
5000 VA
4000 W
3700 W
2800 W
10000 W
95 / 96%
18 / 20 W
2.2 / 3.2 W
24 V: 2+2 M8 bolts
48 V: M8 bolts
29kg / 28kg
595 x 295 x 160mm (24 V)
555 x 295 x 160mm (48 V)

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis