the probe tip
1
Attention!
Please observe that even if the TRITEST
dangerous voltage may be applied to the test object. For determining the absence of voltage, only
use a two-pole voltage tester complying with the DIN EN 61243-3 (VDE 0682-401) standard, e.g. a
DUSPOL
voltage tester.
®
Note on testing insulated lines (figure C):
To localize interruptions of live lines (e.g. a cable break in a cable reel or defective lamps in a chain of
lights), pass the probe tip
other end of the line.
For testing a cable reel, make sure to turn the shock-proof plug by 180° in order to connect both lines
to the phase (external conductor) of a shock-proof socket.
6. Phasesequencetestofathree-phasemains (figure D)
-
The phase sequence test always requires a countercheck during which the phase sequence must
change.
-
Press and hold the blue push-button
-
Press the blue push-button
in red color.
-
Place the probe tip
acoustic signal is emitted and the LED
-
As soon as the LED
(external conductor) L2 within 2 seconds. An acoustic signal is emitted and the LED
green color.
-
As soon as the LED
ce is indicated via the probe tip.
-
probe tip lights in green color: clockwise phase sequence (phase 1 before phase 2)
-
probe tip lights in red color: counter-clockwise phase sequence (phase 2 before phase 1)
-
probe tip flashes in green color: equal phase (phase 1 = phase 2)
-
probe tip flashes in green/red color: phase sequence could not be determined
Note:
Always hold the device steady during the measurements without wobbling.
Mains failures or a lacking mains quality might affect the correct functioning of the device.
7. Batteryreplacement (figure A)
-
Do not apply voltage to the device when the battery compartment is open!
-
Remove the battery compartment cover
the used batteries.
-
Insert new micro batteries (LR03/AAA) into the tester observing correct polarity (positive pole first).
-
Place the battery compartment cover 7 back onto the tester and tighten the screws.
8. Technicaldata
-
regulation: DIN EN 61010-1, DIN EN 61326
-
nominal voltage/frequency range: 200 V to 1,000 V AC/45 to 65 Hz
-
overvoltage category: CAT III 1,000 V/CAT IV 600 V
-
contamination level: 2
-
protection category: IP 53 (DIN EN 60529), protection against dust and water spray
-
automatic switch-off: after approx. 5 minutes
-
operating temperature range: - 10 °C to + 40 °C, air humidity ≤ 75%, 40 °C to + 50 °C, air humidity
≤ 45 %,
03/ 2023
lighting up in red color.
1
along the insulated line from the feeding point (phase) in direction of the
5
again to activate the phase sequence test. The LED
onto the assumed phase (external conductor) L1 for approx. 3 seconds. An
1
4
lights up in green color, connect the probe tip
4
goes out and the acoustic signal is emitted three times, the phase sequen-
easy does not indicate a phase (external conductor), a
®
to switch the tester on. The yellow LED
5
4
flashes in red color.
7
from the tester by loosening the screws and remove
TRITEST
easy
®
must flash.
3
4
must flash
1
with the assumed phase
4
flashes in
12