3 Locking-Unlocking access to programming
By using a "dip-switch" remote (regardless of the type of remotes already memorized) it's possible to lock-unlock access to the program-
ming of the control panel to avoid tampering. The remote setting is the locking-unlocking code verifi ed by the control board.
3.1 Locking access to programming
1. Scroll through the parameters with the buttons
and
until the display shows P008;
2. Access the parameter by pressing the button
3. The display shows alternately the writing
to indicate that the control board
is waiting for the transmission of the block code;
4. Within 10 seconds press CH1 on the "TX Master",
the display shows
to the list of parameters;
5. Access to programming is locked.
WARNING Programming lock/unlock can also be set via Smartphone using the DEAinstaller APP. In this case, an installer code is set
(other than zero) that can only be unlocked via APP.
3.2 Unlocking access to programming
1. Scroll through the parameters with the buttons
and
until the display shows P008;
2. Access the parameter by pressing the button
3. The display shows alternately the writing
to indicate that the control board
is waiting for the transmission of the unlocking
code;
4. Within 10 sec. press the CH1 of the "TX Master",
the display shows
to the list of parameters;
5. Access to programming is unlocked.
3.3 Unlocking access to programming and global reset
WARNING! This procedure involves the loss of all stored set-
tings.
The procedure allows the unlocking of the control panel without
having to know its unlocking code.
Following this release, you must program the control panel again
and adjust all operating parameters, in particular, remember to
properly set the confi guration of parameters (P028 - P029 - P030
– operator confi guration). You will also need to repeat the meas-
urement of impact forces to ensure the installation compliance
to standards.
1. Scroll through the parameters with the buttons
the display shows P008;
2. Access the parameter by pressing the button
3. The display shows alternately the writing
4. Press the button
;
5. Press the button again and hold for 5 seconds (releasing it be-
fore, the procedure is terminated): The display shows the fi xed
writing
followed by
parameters;
6. Access to programming is unlocked.
EN-18
;
before returning
;
before returning
;
, the display shows the fl ashing writing
, before returning to the list of
and
until
;