Funk-empfänger
Vorschau ausblenden Andere Handbücher für RF Rx SW868-4W 24VAC/DC:
Inhaltsverzeichnis
RF Rx SW868/SW915/SW917/SW922-4W 24VAC/DC
//
Montage- und Anschlussanleitung / Funk-Empfänger
Mounting and wiring instructions / Wireless receiver
Instructions de montage et de câblage / Récepteur sans fil
Istruzioni di montaggio e collegamento / Ricevitore wireless
Instruções de montagem e instalação / Receptor sem fio
English
Operation mode
LED 1
LED MD
Standard
flashes
flashes
fast
fast
Relay functions
Standard,
flashes
on
inverse output
fast
Relay energised
on
flashes
fast
Relay energised,
on
on
inverse output
Transmitter functions
Logic function
flashes
on
slowly
Latching
on
flashes
function
slowly
Wiping
flashes
flashes
function
slowly
slowly
Additional functions
Battery
off
flashes
slowly
monitoring
(LED 3
flashes)
Status
off
flashes
monitoring
(LED 4
slowly
flashes)
Detected errors are additionally indicated by flashing of the
assigned channel LED.
Notice
If only one or both additional functions are activated, no further trans-
mitter can be taught in.
Operation mode logic function
- Select logic function. -> LED MD flashes fast.
- Set logic function push-button S2. -> Observe LED display (see table).
- When the desired LED combination is displayed, press push-button
S1 for 1 s.
Function
Relay energised by actua-
tion, relay and transmitter
functions are reset.
Upon actuation: relay is de-
energised. Inverse output
signal.
Relay energised by providing
operating voltage.
Relay energised by providing
operating voltage, inverse
output signal.
The logic functions OR, AND
or Xor are selectable.
Latching function/
Impulse function
Wiping function. After pre-
set time: contact de-ener-
gises automatically.
Relay K3 indicates under-
voltage of the taught-in
and battery-powered
transmitters.
Relay K4 indicates status
error; activates function only
in combination »transmitter
with status signal«.
5 / 24
Logic
LED 1
LED 2
function
OR
on
-
AND
-
on
XOR
-
-
Operation mode wiping contact
- Select wiping function -> LED MD flashes fast.
- Set the time of the wiping contact. The pre-set time can be changed
with push-button S2. -> Observe LED display (see table).
- During mode »wiping time flexible«, count the pulses of the flashing
LED 4 and confirm the time achievement (1 s/pulse) with push-
button S1.
- In order to change set time of the wiping contact, start selection of
operation mode and select wiping function again.
Time of wip-
LED 1
LED 2
ing contact
500 ms
-
-
1 s
on
-
2 s
-
on
5 s
-
-
flexible
-
-
Operation mode status monitoring
- After selection of status monitoring the LED MD flashes
every second.
- The LEDs 1 - 4 indicate the adjustable status times.
- The display of the LED changes every 5 s (see table).
- When the required LED combination is indicated, press the push-
button S1 for 1 s. The desired operation mode is now activated.
- Without confirmation of the selection, the default value of 10 s will
be set.
Status signal
LED 1
LED 2
time
10 s
on
-
100 s
on
on
1 000 s
on
on
10 000 s
on
on
Function: If no status information is given by the taught-in transmit-
ters, relay K4 automatically triggers the alarm after the status time
has elapsed 2.2 times.
Attention! Please ensure that the taught-in transmitter is set to the
correct status signal time.
LED 3
LED 4
LED MD
-
-
flashing
-
-
flashing
on
-
flashing
LED 3
LED 4
LED MD
-
-
flashing
-
-
flashing
-
-
flashing
on
-
flashing
-
flashing
-
LED 3
LED 4
LED MD
-
-
flashing
-
-
flashing
on
-
flashing
on
on
flashing
Inhaltsverzeichnis