Herunterladen Inhalt Inhalt Diese Seite drucken

Panasonic WH-UXZ09KE5-Serie Installationshandbuch Seite 6

Luft/wasser/wärmepumpen|außengerät
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 71
10. Decommissioning
• Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its details.
• It is recommended good practice that all refrigerants are recovered safely.
• Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of recovered refrigerant.
• It is essential that electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that:
• mechanical handling equipment is available, if required,
for handling refrigerant cylinders;
• all personal protective equipment is available and being
used correctly;
• the recovery process is supervised at all times by a
competent person;
• recovery equipment and cylinders conform to the
appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant
can be removed from various parts of the system.
• Electrostatic charge may accumulate and create a hazardous condition when charging or discharging the refrigerant.
To avoid fi re or explosion, dissipate static electricity during transfer by grounding and bonding containers and equipment before charging/discharging.
11. Labelling
• Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant.
• The label shall be dated and signed.
• Ensure that there are labels on the equipment stating the equipment contains fl ammable refrigerant.
12. Recovery
• When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are
removed safely.
• When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed.
• Ensure that the correct number of cylinders for holding the total system charge are available.
• All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant).
• Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order.
• Recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
• The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be
suitable for the recovery of fl ammable refrigerants.
• In addition, a set of calibrated weighing scales shall be available and in good working order.
• Hoses shall be complete with leak-free disconnect couplings and in good condition.
• Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated
electrical components are sealed to prevent ignition in the event of a refrigerant release.
Consult manufacturer if in doubt.
• The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged.
• Do not mix refrigerants in recovery units and especially not in cylinders.
• If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that
fl ammable refrigerant does not remain within the lubricant.
• The evacuation process shall be carried out prior to returning the compressor to the suppliers.
• Only electric heating to the compressor body shall be employed to accelerate this process.
• When oil is drained from a system, it shall be carried out safely.
Attached accessories
No.
Accessories part
Drain elbow
1
Rubber cap
2
6
Qty.
No.
Accessories part
Protective bushing
1
3
8
f) Make sure that cylinder is situated on the scales before recovery
takes place.
g) Start the recovery machine and operate in accordance with
instructions.
h) Do not over fi ll cylinders. (No more than 80 % volume liquid
charge).
i)
Do not exceed the maximum working pressure of the cylinder,
even temporarily.
j)
When the cylinders have been fi lled correctly and the process
completed, make sure that the cylinders and the equipment
are removed from site promptly and all isolation valves on the
equipment are closed off.
k) Recovered refrigerant shall not be charged into another
refrigerating system unless it has been cleaned and checked.
Optional Accessory
Qty.
No.
Base Pan Heater
CZ-NE3P
2
4
It is strongly recommended to install a Base Pan Heater
(optional) if the outdoor unit is install in cold climate area.
Refer the Base Pan Heater (optional) installation instruction
for details of installation.
Accessories part
Qty.
1

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Wh-uxz12ke5-serie

Inhaltsverzeichnis