Label
Fault
Probe1 faulty
E1
(cell)
Probe2 faulty
E2
(defrost)
HIGH temperature
AH1
probe 1 alarm
LOW temperature
AL1
probe 1 alarm
EA
External alarm
OPd
Open door alarm
Defrost
Ad2
due to time-out
Manual activation of the defrost cycle can be started by holding the
If there are no conditions for defrosting:
- the parameter OdO ≠ 0 (EW961, EW971 and EW974)
- the temperature of the evaporator probe Pb2 is higher than the end defrost temperature (EW971 and EW974)
the display will flash 3 times to indicate that the operation will not be carried out.
The alarm condition is always signalled by a buzzer (if present) and the alarm icon
To turn off the buzzer, press and release any key. The relevant icon will continue to flash.
NOTES: If alarm exclusion times are in progress (folder "AL" of the Parameters Table), the alarm is not signalled.
The alarm indicator for probe 1 fault (Pb1) appears
directly on the device display with indication E1.
Models EW971 and EW974: The alarm indicator for probe 2 fault
(Pb2) appears directly on the device display with indication E2.
The instrument is designed for installation on the control panel. Drill a 29x71 mm hole and insert the instrument, fixing it with the special brackets
provided. Avoid installing the instrument in places subject to high humidity and/or dirt; it is suitable for use in environments with ordinary or normal
environmental pollution.
Make sure to ventilate the area near the cooling vents of the instrument.
116
ALARMS
Cause
• values read outside the
operating range
• probe faulty / short-circuited
/ open
• values read outside the
operating range
• probe faulty / short-circuited
/ open
• value read by Pb1 > HAL after
time equal to "tAO".
(See MIN AND MAX TEMP.
ALARMS)
• value read by Pb1 < LAL after
time equal to "tAO".
(See MIN AND MAX TEMP.
ALARMS)
• digital input activated (H11 set
as external alarm)
• digital input activated (H11 set
as external door switch)
(for a time greater than tdO)
• end of defrost due to time-out
instead of reaching the end
defrost temperature detected
by probe Pb2.
MANUAL ACTIVATION DEFROST CYCLE
key down for 5 seconds.
TROUBLESHOOTING
MECHANICAL ASSEMBLY
Effect
• Label E1 displayed
• Alarm Icon/Fixed
• The maximum and minimum
alarm regulator is disabled
• Compressor operation
based on the "Ont" and "Oft"
parameters.
• Label E2 displayed
• Alarm Icon/Fixed
• The defrost cycle will finish due
to Time out (Parameter "dEt")
• Label AH1 recorded in folder
AL
• No effect on adjustment
• Label AL1 recorded in folder AL
• No effect on adjustment
• Label EA recorded in folder AL
• Fixed icon alarm
• Adjustment blocked if EAL = y
• Label Opd recorded in folder
AL
• Fixed icon alarm
• Adjustment blocked
• Label dAt recorded in folder AL
• Fixed icon alarm
.
Solution to problem
• check the probe type (NTC)
• check the probe cabling
• replace the probe
• check the probe type (NTC)
• check the probe cabling
• replace the probe
• Wait for the temperature value
read by probe 1 to drop below
HAL.
• Wait for the temperature
value read by probe 1 to rise
above LAL
• check and eliminate the
external cause which
triggered the alarm on D.I.
• close the door
• delay function defined by OAO
• wait for the next defrost for
automatic return