Instruction for use
Functions
DIP-switch 1 on ON
DIP-switch 2 on ON
DIP-switch 3 on ON
DIP-switch 4 on ON
D+H Mechatronic AG • Georg-Sasse-Str. 28-32 •
Group plug-in card GE 514, GE 514-S
Group plug-in card GEL 542, GEL 542-S
for Smoke Vent Control Panel RZN 43xx-E (GE 514, GE 514-S)
and Ventilation Control Panel (GEL 542, GEL 542-S)
GE
514
F6,3A
GE 514, GE 514-S
- group plug-in card for control of smoke and heat
vent drives/ NSHEVs in conjunction with LE 513
- available in 2 versions
- GE 514 (8A)
- GE 514-S (10A)
The vent closes completely after the vent button has been pressed once.
If DIP-switch 1 is OFF, the vents will only close as long as the vent button is pressed. After that it is no longer
possible to close the vents using the smoke/ heat vent buttons or REM 42 or WRG 82
The vent opens completely after the vent button has been pressed once.
If DIP-switch 2 is OFF, the vents will only open as long as the vent button is pressed.
The vent closes completely at position "
temperature control if connected with WE 516).
If DIP-switch 3 is OFF, a closing about "central close" is not possible.
The vent opens completely at position "
control if connected with WE 516).
D-
22949 Ammersbek • Tel.
GE
514 S
F10A
O N
1
2
3
4
GEL 542, GEL 542-S
- group plug-in card for ventilation control
of drives
- available in 2 versions
- GEL 542 (8A)
- GEL 542-S (10A)
master-closing
" (wind, rain, timer, major-closing switch and room
master-opening
" (timer, major-opening switch and room temperature