Herunterladen Inhalt Inhalt Diese Seite drucken

Installation Diagram; Drain Piping For Outdoor Unit; Accessories - Mitsubishi Electric SUZ-SWM VA-Serie Installationshandbuch

Vorschau ausblenden Andere Handbücher für SUZ-SWM VA-Serie:
Inhaltsverzeichnis

Werbung

3. Installation diagram

3.1. Outdoor unit (Fig. 3-1)
Ventilation and service space
A 100 mm or more
B 350 mm or more
C 500 mm or more
When the piping is to be attached to a wall containing metals (tin plated) or metal
netting, use a chemically treated wooden piece 20 mm or thicker between the wall
and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping.
Units should be installed by licensed contractor accordingly to local code re-
quirement.
SUZ-SWM80VA2, SUZ-SWM80VAH2, SUZ-SWM100VA,
SUZ-SWM100VAH, SUZ-SHWM60VAH
en
A
de
C
417.5
Air inlet
Air inlet
175
4. Drain piping for outdoor unit (Fig. 4-1)
Drain socket
5
C
A
B
81
840
Drainage hole
({42)
40
Air outlet
500
Drain hose
Fig. 4-1
Note:
When operating the air to water heat pump in low outside temperature, be sure
to follow the instructions described below.
• Never install the outdoor unit in a place where its air inlet/outlet side may be ex-
posed directly to wind.
• To prevent exposure to wind, install the outdoor unit with its air inlet side facing
the wall.
• To prevent exposure to wind, it is recommended to install a baffle board on the air
outlet side of the outdoor unit.
SUZ-SWM30VA, SUZ-SWM40VA2, SUZ-SWM60VA2,
SUZ-SHWM30VAH, SUZ-SHWM40VAH
(mm)
Air inlet
Fig. 3-1

4.1. Accessories

Check the following parts before installation.
<Outdoor unit>
1
Drain socket
• Provide drain piping before indoor and outdoor piping connection. (It will be hard
to install drain socket
to drain piping as outdoor unit becomes immovable.)
• Connect the drain hose
shown in the figure for drainage.
• Make sure to provide drain piping with a downhill grade for easy drain flow.
Note:
Do not use the drain socket
makes the fan stop.
Drain socket is not included in the SHWM series.
C
A
C
81
800
400
Drainage hole
SUZ-SWM30VA/40VA/60VA2: {42
Air inlet
SUZ-SHWM30/40VAH: {33
40
Air outlet
150
500
if indoor and outdoor piping connection is conducted prior
1
(obtainable at a store, inside diameter: 15 mm) as
in the cold region. Drain may freeze and it
1
A
B
(mm)
1

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis