Installation Work

Please install the central control after turning off the power for fear of electric shock.
Please arrange or protect the wiring so that excessive force is not applied to the electrical wires.
Control PCBs (printed circuit boards) are mounted to both the top and bottom cases.
Be careful that you do not damage the PCBs when using a screwdriver and other tools.
The PCBs can be damaged by static electricity, and so be sure to discharge any static electricity accumulated on your body
before starting the work.
(Static electricity can be discharged by touching the control board and other grounded parts.)
Installation Place
Please install in an indoor location that is not exposed to electromagnetic waves, water, dust, or other foreign substances.
The operating temperature range of this product is from 0°C to 40°C.
Install in a location where the ambient temperature remains within the operating temperature range.
However, if the operating temperature range is exceeded, be sure to implement corrective measures such as installation of a
cooling fan.
Be aware that continued usage of this central control outside the operating temperature range can result in operation problems.
Space Required for Installation
18.5
13
The dotted lines show the installation opening section for installation on the
control board (the dimensions are only an example).
(1) In case of installing on the control board
Please be sure to lock the control board to protect persons
from the electric shock.
Avoid usage of heat-retaining materials and heat-insulating
materials because these can result in heat buildup and
adversely affect the operation of the central control.
(2) In case of embedding in a wall
Please check that there is sufficient space inside the wall.
If the temperature inside the wall exceeds 40
central control on the control board.
When performing the continued installation of multiple controllers, be sure to obtain the distance between units and
service space as shown in the figure.
50mm or
more
215
(18.5)
152
(13)
Installation opening
178
50mm or
50mm or
more
more
215mm
Service Space
Front of central control
500mm or more is needed
Bottom of central control
150mm or more is needed
M4 pilot hole
Left, right and top of central
4 locations
control
50mm or more is needed
Central control
outline
Caution
Please do not install devices that can cause the ambient temperature to
rise in the same control board. Also, do not install multiple controllers in the
same control board. These can cause heat to build up and result in false
operation. If multiple central control must be installed in the same control
board, take corrective measures to ensure that the temperature in the
control board does not rise above 40°C such as by installing cooling fans.
°C
, install the
150mm or
more
120mm
50mm or more
500 mm or more
150mm or more
Internal wall
Lead-in wires
Building's wall
Electrical box
50mm or more
(prepared on site)
Internal wall or
front side of the