show
extsensor {port_num} {sen_type} {sen_field}
publish mode set {NONE=0|INTERVAL=1|
DELTA=2|INTERV_DELTA=3}
extsensor {port_num} {sen_type} {sen_field}
publish mode show
extsensor {port_num} {sen_type} {sen_field}
publish mqtt retain set {OFF=0|ON=1}
extsensor {port_num} {sen_type} {sen_field}
publish mqtt retain show
extsensor {port_num} {sen_type} {sen_field}
publish timer set {num_secs}
extsensor {port_num} {sen_type} {sen_field}
publish timer show
extsensor {port_num} {sen_type} {sen_field}
publish delta set {float}
extsensor {port_num} {sen_type} {sen_field}
publish delta show
extsensor {port_num} {sen_type} {sen_field}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} port set {port_num}
extsensor {port_num} {sen_type} {sen_field}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} port show
extsensor {port_num} {sen_type} {sen_field}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} state set {OFF=0|ON=1|
DISABLED=2}
extsensor {port_num} {sen_type} {sen_field}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} state show
extsensor period set {24H=0|12H=1|2H=2|1H=3|
30MIN=4}
extsensor period show
http
http server set {HTTP_BOTH=0|HTTPS_ONLY=1|
HTTP_ONLY=22|HTTPS_REDIR=3}
http server show
http port set {ip_port}
http port show
http portssl set {ip_port}
http portssl show
http tls mode set {TLS12=0|TLS13_12=1|
TLS13=2|TLS13_12_11=3}
http tls mode show
http ajax enabled set {OFF=0|ON=1}
http ajax enabled show
http passwd enabled set {OFF=0|ON=1}
http passwd enabled show
http passwd local set {OFF=0|ON=1}
http passwd local show
http passwd radius set {OFF=0|ON=1}
http passwd radius show
http passwd user set "{passwd}"
http passwd admin set "{passwd}"
http passwd hash user set "{passwd}"
http passwd hash admin set "{passwd}"
input
input {port_num} state show
input all state {MODE0=0|MODE1=1|MODE2=2}
show
input {port_num} name set "{name}"
input {port_num} name show
input {port_num} invert enabled set {off=0|on=1}
input {port_num} invert enabled show
input {port_num} label {LOW=0|HIGH=1} set
"{name}"
input {port_num} label {LOW=0|HIGH=1} show
input {port_num} events set {off=0|on=1}
input {port_num} events show
input {port_num} events type set
"{EVT_SYSLOG=0,EVT_SNMP=1,EVT_EMAIL=2
,EVT_SMS=3,EVT_GSMEMAIL=4,EVT_BEEPER
=5,EVT_DISPLAY=6,EVT_CONSOLE=7}"
input {port_num} events type show
Expert Net Control 2111/2191
sets publish mode
shows publish mode
sets mqtt retain
shows if mqtt retain set
sets publish time interval
shows publish time interval
sets publish delta value
shows publish delta value
sets Port for Power Port Switching actions
shows Port for Power Port Switching actions
sets Port state for Power Port Switching actions
shows Port state for Power Port Switching actions
sets sensor Min/Max measurement period
shows sensor Min/Max measurement period
enters cmd group "http"
sets accepted connection types
shows accepted connection types
sets http port
shows http port
sets https port
shows https port
restricts TLS mode
shows TLS mode restriction
enables ajax autorefresh on/off
shows if ajax autorefresh enabled
enables http password on/off
shows if http password enabled
enables local login on/off
shows if local login enabled
enables login for RADIUS on/off
shows if RADIUS login enabled
sets http user password
sets http admin password
sets hashed http user password
sets hashed http admin password
enters cmd group "input"
shows input state
shows input state of all ports in 3 different view
modes
sets sensor name to label
shows label of sensor
inverts input on/off
shows if input inverted
sets input low/high text
shows inputs low/high text
enables input events on/off
shows if input events are enabled
enables different event types
shows what event types are enabled