TECHNICAL DATA
Thermal power – output
Fuel
Electrical supply
Motor
Capacitor
Ignition transformer
Pump
Absorbed electrical power
Burner with CE marking in conformity with EEC directives: Machine Directive 2006/42/EC, Low Voltage
◆
Directive 2006/95/EC, Electromagnetic Compatibility 2004/108/EC and Efficiency 92/42/EEC.
The burner meets protection level of IP X0D (IP 40), EN 60529.
◆
CE Certification No.: 0036 0259/99 as 92/42/EEC.
◆
1 – Return line
2 – Suction line
3 – Gauge connection
4 – Pressure regulator, 2
5 – Vacuum gauge connection
6 – Hydraulic jacks with air-damper
7 – Combustion head adjustment screw
8 – Lock-out lamp and reset button
9 – Flange with insulating gasket
10 – Regulation pressure, 1
11 – Economizer
2355
All manuals and user guides at all-guides.com
71 / 95 – 240 kW
Light oil, max. viscosity at 20 °C: 6 mm
Single phase,
Run current 1.5 A – 2750 rpm – 288 rad/s
5 µF
Secondary 8 kV – 16 mA
Pressure: 7 – 15 bar
0.33 kW
Fig. 1
D8078
EQUIPMENT
Quantity
nd
stage
st
stage
1
–
6 / 8 – 20 kg/h
~
230 V
±
10%
50Hz
Description
2
Flexible pipes with nipples
1
Flange with insulating gasket
4
Screws and nuts for flange
1
Maintenance assembly
1
Screw with two nuts for flange
1
4 pin plug
GB
2
/s (1.5 °E)