Herunterladen Inhalt Inhalt Diese Seite drucken

IFM Electronic efector 160 LK10 Bedienungsanleitung Seite 43

Elektronischer füllstandsensor
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Applications
Pumping station
Empty the tank with overflow protection
Switching output 1: control to empty tank
upper value exceeded → submersible pump ON
lower value reached → submersible pump OFF
hysteresis function, normally open (Hno)
Switching output 2: overflow protection
maximum value exceeded → alarm
slightly below SP2 (to suppress wave movements)
hysteresis function, normally closed (Hnc)
display value
• If SP1 is exceeded, output 1 switches (submersible pump ON). When the
level is below rP1 again the output switches back (submersible pump OFF).
• If SP2 is exceeded or if there is a wire break, output 2 switches off.
empty
overflow
protection
43

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis