Mounting
L (probe length)
M (mounting zone)
• Fasten mounting elements within zone M.
• Mounting elements must be fixed above the measuring segment
OP and at a minimum distance to OP (see value y, measured to the
middle of the segment).
• The probe must comply with minimum distances to the tank wall,
metallic objects in the tank (B), tank bottom and further level sen-
sors. The distances x, y and w depend on the medium set (MEDI).
MEDI = CLW1
cm
x
2.0
y (LK1022)
2.5
y (LK1023)
4.5
y (LK1024)
6.0
u
1.0
v
4.5
w
4.0
LK1022
cm
inch
26.4
10.4
14
5.5
MEDI = CLW2, OIL1
inch
cm
0.8
3.0
1.0
3.5
1.8
5.5
2.4
7.0
0.4
1.0
1.8
4.5
1.6
5.0
LK1023
cm
inch
47.2
18.6
23
9.1
MEDI = OIL2
inch
cm
1.2
4.0
1.4
4.5
2.2
6.5
2.8
8.0
0.4
1.0
1.8
4.5
2.0
6.0
LK1024
cm
inch
72.8
28.7
36
14.2
inch
1.6
1.8
2.6
3.2
0.4
1.8
2.4
29