Herunterladen Inhalt Inhalt Diese Seite drucken

Minimum Alarm (↑): [550 Mv]; Maximum Alarm (↑): [750 Mv]; Test Mode - swim-tec CL2 Deluxe WiFi 2,4 l/h Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für CL2 Deluxe WiFi 2,4 l/h:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
concentration) we are not able to give a basic setting. It will thus not necessarily
correspond to the factory setting of the setpoint. After about 2-3 weeks or every refill,
the setpoint must be compared with the desired chlorine value and adjusted as required
since the effective Redox value is only established when the system is under operation.
If the actual value undercuts the setpoint, the system automatically doses chlorine until
the setpoint is achieved. Then the dosing pump switches itself off.
5.3 Rx p band: [100 mV]
The value in figures gives the proportional band, thus the regulation slope. The usual
value is 100 mV.
Meaning: With a p band of 100 mV, the dosing pump operates at maximum performance
with a deviation of the measured value compared to the setpoint of Δ 100 mV. When
the actual value approaches the setpoint in the p band, the dosing performance is
reduced proportionally. Thus, for a deviation of e.g. Δ 50 mV, the pump only operates
with 50 % of the maximum performance.
5.4 Minimum alarm (↑): [550 mV]
Minimum alarm value which, when undercut, will trigger an alarm.
5.5 Maximum alarm (↑): [750 mV]
Maximum alarm value which, when exceeded, will trigger an alarm.
6

Test mode

Functional test of all inputs and outputs - Only to be used by authorised specialist
staff!
WARNING!
-
Pump for pH
-
Pump for disinfection Activate using the arrow buttons
-
Alarm relay
-
Level of pH
-
Level of disinfection
-
Flow sensor
-
Flow rate
-
Input pH
-
Input Rx
-
Input Temp
-
Input CL (CLE 3)
-
Input CL (CLB 2)
This is a functional test!
Activating the pumps for pH or disinfection may
result in dangerous over-dosing!
Activate using the arrow buttons
Activate using the arrow buttons
Close/open display
Close/open display
Close/open display
Functional test of connection for flow meter
Display pH value in pH and mV
Display Rx value in mV
Display of temperature in °C
Not relevant for pH/Rx
Not relevant for pH/Rx