1. descriPtiOn OF stOrage tanKs

The CORSUN 1 tanks feature one coil integrated into their upper section that transfers the
heat collected by the solar sensors to the domestic hot water of the tank.
The CORSUN 2 tanks feature 2 integrated coils: the lower coil transfers the heat collected
by the solar sensors to the domestic hot water of the tank and the upper coil transfers the
EN
heat from backup energy when there is insufficient solar energy.
The CORFLOW tanks feature 1 high output coil for connection to a boiler.
Two lifting rings at the top of the tank allow it to be moved by crane. To access the 2 lifting
rings on the reservoirs with unclassified casing, you must remove the hood at the top.
CORSUN 1, CORSUN 2 and CORFLOW tanks have external rust protection with a layer of
paint.
maximum water use temperature: 95 °c
service pressure: 8 bar (or 10 bar as an option).
Thermal insulation of the water tanks is made either:
- for version m0, of a hard gray casing with 100 mm glass wool insulation.
- for version m1, of a soft, insulated, 100-mm-thick glass wool casing covered with a soft
PVC jacket (non-flammable).
- for the unclassified version, of a soft, insulated, 100-mm-thick foam casing covered
with a soft PVC jacket.
Versions M1 and M0 are delivered in 2 packages:
- The tank comes in a bubble-wrapped pallet,
- The insulated casing comes in a cardboard box.
The delivery is in 1 package for the unclassified versions: Casing is installed on the tank.

2. setting uP the aPPLiance

• 2 lifting eyebolts on the upper part of the tanks allow them to be positioned by a
crane. using tapping connections is prohibited since damage would be caused to
the internal coating.
• Place the tank and its safety unit (and/or safety valve) sheltered from frost.
• Position it as close as possible to the main draw-off points.
• If it is placed outside the inhabited area, insulate the pipes. If the equipment is to be
installed in a room where the ambient temperature is always over 35°C, provide ventilation
for the room.
• Ensure that the support element is suitable to hold the weight of the tank when it is full of
water.
• Provide opposite the cover a minimum space of 1 metre opposite the flange (or the
manhole) for periodic tank maintenance.
• Install a retention tank with the drainer under the tank when it is placed in an attic or above
inhabited dwellings.
• The safety unit and/or safety valve must be accessible.
• A sewer drain equipped with a gripper is necessary.
• The lower tapping connection allows the tanks to be completely drained.
• The tanks only work in vertical position.
Page 24 / 60
CORSUN 1 & 2 / CORFLOW
CP090497-B