COMBUSTION HEAD SETTING (see fig. 12, page 6)
It depends on the output of the burner and is carried out by rotating clockwise or counterclockwise the set-
ting screw (6) until the set-point marked on the regulating rod (7) is level with the outside plane of the
nozzle-holder assembly (1).
– In the sketch the combustion head is set for an output of 2.25 GPH at 15 bar.
The set-point 2.5 of the regulating rod is at the same level with the outside plane of the nozzle-holder as-
sembly as shown in the schedule.

4.2 ELECTRODES ADJUSTMENT

ATTENTION
Lean the diffuser disc-holder
assembly (1) on the nozzle-
holder (2) and lock it by screw
(3). For prospective adjust-
ments loosen screw (4) and
move the electrodes assembly
(5), (see fig. 13).
To have access to the electrodes
carry out operation as described in
chapter 4.1 (page 6) "RECOM-
MENDED NOZZLES".

4.3 PUMP PRESSURE AND AIR OUTPUT

st
1
STAGE ADJUSTMENT
ADJUSTMENT OF AIR SHUTTER:
Unloosen the nut (1), turn the screw (2) until the indicator (3) reaches the
position desired. Then lock the nut (1), (see fig. 14).
PRESSURE REGULATION:
This is set at 9 bar at the factory.
Should it be necessary to re-set or alter such pressure, this can be done, by
adjusting screw (7).
The pressure gauge must be mounted in place of cap (8), (see fig. 15).
2
nd
STAGE ADJUSTMENT
ADJUSTMENT OF AIR SHUTTER:
Unloosen the nut (4), turn the screw (5) until the
indicator (3) reaches the position desired.
Then lock the nut (4), (see fig. 14).
PRESSURE REGULATION:
This is set at 15 bar at the factory.
Should it be necessary to re-set or alter such pres-
sure, this can be done, by adjusting screw (9).
The pressure gauge must be mounted in place of
cap (8), (see fig. 15).
When burner shuts down the air damper automati-
cally closes till a max. chimney depressure of
0,5 mbar.
2332
0
4.5
– 0.5 mm
Fig. 13
D5341
7
GB
WARNING
MEASURES MUST BE
RESPECTED
4
5
3
2
1
Fig. 14
Fig. 15
6 – 7