NB! Due to the potential danger of ther-
mal embrittlement, it is forbidden to use
a PVC-insulated cable as the connection
cable for the sauna climate device.
• The internal connections of the device
are made by means of screw terminals
according to Figure 3 (see page 31)
and Table 1 (see pages 10–11) in this
manual.
• Protective earthing (PE) must be con-
nected to the connection terminal of
the device, with the cross- sectional
area of the cable being at least
2.5 mm2.
• The heater must be powered from
the 380 VAC (3-phase) or 230 VAC
(1-phase) 50/60 Hz supply circuit
through a control device protected
by an over-current fuse of the size
shown in Table 1 (see pages 10–11).
• If you want to connect the air circu-
lation fan of the device sepa rately
from the heater control device,
the fan must be connected via a
residual-current device. In this case,
the protective earthing (PE) of the
fan supply input terminal of the
sauna climate device must not be
brought into contact with the pro-
tective earthing of the heater sup-
ply input terminal. In this case, use
earthed cables of at least 1.5 mm2 to
power the fan.
• The power cable must enter the
housing of the sauna climate device
so that the water does not flow along
32
the cable into the electrical connec-
tion box of the housing of the sauna
climate device. The outer insulation
of the cable can only be peeled
off only from the part that is in the
device housing.
• If the connecting and installation
cables are located higher than
1000 mm from the floor of the sauna
room or inside the walls of the sauna
room, they must be able to withstand
a temperature at least 170 °C (e.g.,
SSJ). Electrical equipment installed
in the steam room below 1000 mm
must withstand a temperature of at
least 125 °C (e.g., T125).
• The recommended cross-section
of the connection cable grooves is
given in Table 1 (see pages 10–11).
NB! The sauna climate device may only be
connected by a professional electrician in
accordance with the applicable regulations!
Optional !
Connecting the fan
directly from the
electric panel if
adjustment from the
control panel is not
recommended.
FAN
!!!
3x 1.5 Ø
5x 2.5 Ø
CONTROL
UNIT IP65

ELECTRIC PANEL

TEMPERATURE
SENSOR (LOCATION
ACCORDING TO THE
MANUFACTURER'S
REQUIRMENTS)
CONTROL
PANEL
HEATING ELEMENTS

DOOR SENSOR

(2x Ø 0.34 mm2)
33