6. Faults
Fault
Wrong output signal
Wrong output signal and too long
response time
EN
Signal span too small
Signal span drops
24
All manuals and user guides at all-guides.com
Possible cause
Sensor drift caused by chemical attack
Wrong mounting geometry, for example
mounting depth too deep or heat dissipation
too high
Deposit on the probe
Power supply too high/low
Moisture has entered
Measure
Check media compatibility
Move the temperature-sensitive area of the
probe into the medium
Remove deposit
Rectify the power supply
Fit the cable correctly