Step 3: Duct and accessories installation
1. Install the filter (optional) according to
the size of the air inlet.
2. Install the canvas tie-in between the body
and duct.
3. The air inlet and air outlet duct should
be far enough apart enough to a avoid
air passage short-circuit.
4. Connect the duct according to
the following diagram:
Canvas tie-in Canvas tie-in
Air outlet
Isolation booth
5. Refer to the following static pressure
guidelines when installing the indoor unit.
Table.4-2
MODEL
(Btu/h)
12K
18K
24K
30K~36K
42K~60K
Change the fan motor static pressure
according to external duct static pressure.
Isolation booth
Air inlet
Air dust filter
checking orifice
Fig. 4.10
Static Pressure
(Pa/in.wg)
0~50/0~0.2
0~100/0~0.4
0~160/0~0.64
0~160/0~0.64
0~160/0~0.64
NOTE:
1. Do not place the connecting duct weight on
the indoor unit.
2. When connecting the duct, use a
nonflammable canvas tie-in to prevent vibrating.
3. Insulation foam must be wrapped outside the
duct to avoid condensate. An internal duct
underlayer can be added to reduce noise, if the
end-user requires.
4. The min. length of the duct should be more
than 1m, and fix on the air inlet by screws
(applicable to the unit that the air inlet filter is
not fasten by screws).
Step 4: Adjust the air inlet direction
(From rear side to under-side.)
1. Take off the ventilation panel and flange.
Ventilation panel
2. Change the mounting positions of the
ventilation panel and air return flange.
Air return flange
Air return flange
Fig. 4.11
Ventilation panel
Fig. 4.12
Page 11