3.5.4

Electrostatic discharge

Electrostatic discharge can irreparably damage the electronic components.
Only touch the connector pins and connection wires if your body is suit-
ably earthed, for example via an ESD wrist strap:
3.5.5

Cable routing

The connection cable may be damaged if bent excessively.
Pay attention to the minimum bending radius (see
→ page
3.6

Instructions on electromagnetic compatibility

To improve the electromagnetic environment, please observe the following installation
instructions:
 Only use connectors with a metal housing or a housing made of metallised plastic,
as well as screened cables.
 Connect the screen, if foreseen in the screening concept, to the connector housing.
 Connect the screens using large area connections.
 Keep all unscreened cables as short as possible.
 Design the earth connections with a large cross-section (e.g. using a low inductance
earth strap or flat conductor) and keep them short.
 If there are potential differences between machine earth connections and electronic
earth connections, ensure no equalising currents can flow over the cable screen.
For this purpose, e.g. lay an equipotential bonding cable with a large cross-section
or use cable with separate double screening. In case of cables with separate double
screening, only connect the screens at one end.
GEL 27xx
EMC instructions