Maintenance Intervals
Check explosion-protected components regularly to ensure that its fitting, installation and
operation are in accordance with the regulations.
Refer to the corresponding national regulations (e.g. EN 60079-14) for the type and
scope of tests. The maintenance intervals must be chosen, such that the occurrence of
deficiences, anticipated in the system, can be avoided.
Note the following when establishing the intervals between checks:
the operating conditions (degree of utilization of the Miniatur Circuit-Breaker, malope-
ration)
manufacturers' instructions in technical documentation (mechanical and electrical ser-
vice life)
major changes in the whole system (e.g. changes of zone allocation)
Remedial action
Any defects, which affect the explosion protection, must be remedied immediately:
Take the device out of operation! (Disconnect it from the supply!)
Remedy the defects !
Put the device into operation.

11 Transport and Storage

Transport and Storage are only permitted in the original packing.
12 Disposal
Observe the national standards for refuse disposal.
149915 / 8562606300
S-BA-8562-03-en-20/11/2008
Transport and Storage