Installation

8.1 Mains Connection

Connect the cables with particular care.
Choose suitable cables and route them accordingly to ensure that the maximum
permissible conductor temperatures are not exceeded.
To ensure that creepage distances are maintained remove precisely 10, 17 or 21 mm of
insulation (see chapter "Mains Connection").
The conductor must not be damaged (scored) when stripping the insulation!
Only heat-resistant cables must be used, if connected directly.
8.2 Rated connection cross-section
Solid, stranded or finely stranded copper wires can be used. 1 or 2 wires of the same
cross-section can be fitted under one terminal. Both wires must be made of the same
material. No preparation is necessary prior to connecting the wires.
When terminal sleeves are fitted, they must be gas-tight and applied with a suitable tool.
Conductor
single-wire
stranded or flexible-stran-
ded
Permissible tightening tor-
ques for the options mentio-
ned*
*Permissible tightening tor-
ques for 10 mm
cable
149915 / 8562606300
S-BA-8562-03-en-20/11/2008
Main contact terminals
2 x 1.5 ... 10 mm
2 x AWG 16 to 8
1 x 10 mm
(bend the end of the conduc-
tor)
2 x 1.5 ... 6 mm
2 x AWG 16 to 10
1.8 ... 2.0 Nm
16 ... 18 lb.in
2.5 Nm
2
single-wire
23 lb.in
Auxiliary contact terminals
2
*
2 x 0.75 ... 2.5 mm
2 x AWG 18 to 13
04935T00
2
04938T00
04939T00
2
2 x 0.75 ... 1.5 mm
2 x AWG 18 to 16
04940T00
1.0 ... 1.2 Nm
9 ... 11 lb.in
Residual current circuit-breaker with
integral overcurrent protection
8562/5
Installation
2
04937T00
2
04941T00
9