System test
GMC Board Alarm Codes
There is an LED on the GMC board that displays any board errors.
following table. In the case of more than one error, the error with
the highest priority will be displayed until it is resolved.
In the case of normal operation, the LED flashes at a frequency of ½
Hz. In the case of an error, the LED remains off for 4 seconds, then at
a frequency of 1Hz, it flashes a number of times equal to the error
Fault
Description
Code
2
Safety Input
3
Enter water Temperature Sensor (EWT)
4
Actual Refrigerant Temperature Sensor (TR)
5
Outdoor Air Sensor of GMC
6
Loss communication to NUI control
7
NUI control Room Sensor
9
10
13
14
Loss of Signal From inverter board or High Temperature Release
15
Exit water Temperature Sensor (LWT)
16
Alarm Test
17
Inverter Air Sensor (TO)
18
G-Tr inverter short circuit protection
20
Compressor position Detection Circuit error
21
Inverter Current Sensor error
22
Heat Exchanger Sensors (TE) / (TS)
23
Discharge Temperature Sensor (TD)
24
Outdoor Fan motor error
26
Other unit error
27
Compressor Lock
28
Discharge Temperature error
29
Compressor Breakdown
14
30AWH
All manuals and user guides at all-guides.com
code and than remains off again for 6 seconds. If the error code
has 2 digits, the flashing is interrupted for 2 seconds between the
Example: error 23: LED off for 4 seconds. 2 flashes at a frequency
of 1Hz. Off for 2 seconds. 3 flashes at a frequency of 1Hz. Off for
6 seconds. The cycle repeats until the LED turns off because the
problem is resolved or if an error with higher priority occurs.
(Fig. 16)