The 30AWH units drive a 3-way valve to manage a sanitary water
accumulation tank. The operating logic provides that, in the
case of a request for sanitary water by an accumulation tank, the
system controls a 3-way valve to direct the hot water only to the
tank and to operate at the maximum capacity to provide water at
60 °C (compatible with the operating envelope).
power the valve (1ph ~ 230V, 2A max), and a command signal
Frequency Limitation
To force the unit to operate at a lower maximum frequency
(to reduce noise) in the absence of a User Comfort Interface,
provide a Dry Contact (contact quality greater than
(see Fig. 17). With the contact closed, the unit will operate
with a maximum frequency lower than the standard one,
Stop Unit or Defrosting signals
There are several signals available on the terminal strip to indicate
particular conditions or the stop of the external unit.
The available signals are:
the external environmental conditions, the unit could perform
defrosting cycles to clean the external battery of any ice
formations. Under these conditions, it is not possible to guarantee
the requested temperature output water temperature, which
could reduce general comfort.
If the positioning of the external unit could induce a non-
representative reading of the external temperature by the
probe positioned on the machine, an additional temperature
Dehumidifier or Humidifier
using humidity sensor into 33AW-CS1 interface.
All manuals and user guides at all-guides.com
The sanitary water request signal must be a Dry Contact type
(contact quality greater than 25mA @ 12V) that closes the circuit
Attention: The sanitary water request has higher priority than
the programmed operating mode in both heating and cooling
mode.
otherwise it will operate in standard mode.
using parameters 5 and 6 from the User Interface menu of
the 33AW-CS1.
The maximum noise reduction is about 3dB at 75% of the
maximum operating frequency of the compressor.
User Comfort Interface (NUI), and operating with this interface, a
signal is provided that indicates that the pre-set temperature has
been reached. This signal can be used as the contact window
Several outputs are used for more than one condition. It is possible
installation menu (refer to the 33AW-CS1 manual).
Refer to the tables on page 10 for the correct pin-outs and use of
the signals.
probe can be provided (NTC 2 wire, 3kΩ @ 25°C, Carrier code:
33AW-RAS01) remote. Connect the terminals of the probe
Configure ambient humidity limit (NUI CODE 107) where
5% hysteresis)
NUI
(Fig. 17)
30AWH
9