Note:
Incorrect programming of times is automatically prevent-
ed so that the switching processes are not confused.
If you have, e.g., set a temperature of 20.0 °C from 06:00
onwards in memory slot "P1" and a temperature of 18.0 °C
from 09:00 onwards in memory slot "P2", the memory slot
"P3" cannot be programmed to any time before 09:10.

c) Function G3 "PROGRAM SETBACK"

If you want to change the temperature value of all programmes,
e.g., by 1 °C, you do not need to change the entire programming.
You only need to set a correction value (-3.0 °C......+3.0 °C) in
the function G3 "PROGRAM SETBACK".
If you then check your temperatures in function G2 "PROGRAM
SETTING", the value corrected accordingly is displayed there.
Example:
In programme "P1", the time set is 06:00 and the temperature
value is 20.0 °C.
After programming "-1.0 °C" in the function "PROGRAM SETBACK",
the temperature value in programme "P1" is now 19.0 °C.
If you set "0.0 °C" again in the function "PROGRAM SETBACK", the
programme "P1" sets a temperature of 20.0 °C again.
Proceed as follows:
1.
After selecting this function G3 "PROGRAM SETBACK" and
confi rming with "OK" (2), the temperature correction value
fl ashes in the display.
2. Set the correction value (-3.0 °C......+3.0 °C).with the buttons
"–" (5) and "+" (6).
3. Confi rm the setting with "OK" (2).
The room thermostat is then in the previous menu for selec-
tion of functions again.
4. To leave the menu and return to the regular display, push the
button "MENU" (3), repeatedly if required.
63