10 Diagnose
Diagnose-Code
Definition
0x5100
General power supply fault – Check availability
0x5101
Fuse blown/open – Exchange fuse
0x5102 to 0x510F
Reserved
0x5110
Primary supply voltage overrun – Check tolerance
0x5111
Primary supply voltage underrun – Check tolerance
0x5112
Secondary supply voltage fault (Port Class B) – Check
tolerance
0x5113 to 0x5FFF
Reserved
0x6000
0x6001 to 0x631F
Reserved
0x6320
Parameter error – Check data sheet and values
0x6321
Parameter missing – Check data sheet
0x6322 to 0x634F
Reserved
0x6350
Reserved
0x6351 to 0x76FF
Reserved
0x7700
Wire break of a subordinate device – Check installation
0x7701 to 0x770F
Wire break of subordinate device 1 ...device 15 – Check
installation
0x7710
Short circuit – Check installation
0x7711
Ground fault – Check installation
0x7712 to 0x8BFF
Reserved
0x8C00
Technology specific application fault – Reset Device
0x8C01
Simulation active – Check operational mode
0x8C02 to 0x8C0F Reserved
0x8C10
Process variable range overrun – Process Data uncertain
0x8C11 to 0x8C1F
Reserved
0x8C20
Measurement range exceeded – Check application
0x8C21 to 0x8C2F Reserved
0x8C30
Process variable range underrun – Process Data uncertain
0x8C31 to 0x8C3F Reserved
Handbuch PROFINET
Version 1.2 05/2021
10.4 Tabelle mit IO-Link Device
Diagnose-Codes
Typ
Error
Error
Warning
Warning
Warning
Error
Error
Error
Error
Error
Error
Error
Warning
Warning
Error
137