4.4
Ensure ATEX requirement
ATEX pump connection with equipotential bonding
The following additional requirements must be taken into account for the electrical installation so that the pumps may be
operated in a potentially explosive atmosphere.
Cable cross-section
The mains cables to the control unit require a minimum cross-section of 6 mm
whichever cross-section is larger (see "Technical data", page 29).
An earthing cable of at least 4 mm
EN 60079-14. The earthing cable is routed between the (self-locking) earthing screw and the screw retainer on the terminal.
To do this, proceed as follows:
Before connecting the pump, check whether the motor protection switch of the control unit is suitable for the power con-
sumption of the pump(s) (see type plate).
This system's ATEX pumps can have a 6 or 9-wire cable. Double assignment of the phases in the control unit is provided
for 9-wire cables.
Printed board connections for the wastewater pump(s) (ATEX)
Route the green-yellow earthing cable from the pump to
the control unit and feed into the control unit via a sepa-
rate cable gland (enclosed).
Set the motor protection switch to the nominal current of
the pump (see type plate of the pump).
U1, V1, W1 (U2, V2, W2
): Phases
*
PE: protective conductor
T1,T2: temperature monitoring
*
Only 9-wire variant
.
**
Systems which are to satisfy the ATEX requirement must be connected to terminal block T2 (NOT self-resetting)
010-990
must be connected to the submersible pump for the equipotential bonding according to
2
**
Installation and operating instructions
or according to the required fusing,
2
31 / 140