Translated from the originalinstructions
1

- WARNING

Transport
For information regarding the delivery of units, please refer to
the "General Conditions of Sale."
Units must be transported and handled in compliance with the
indications on their packaging (number of stacked units,
direction, etc.).

Installation

This unit and all related equipment must be installed by
qualified personnel.
The standards applicable in the country in which the unit is
installed and the accepted practices for refrigerant and
electrical connections must be respected.
TECUMSEH cannot be held liable if installation and mainte-
nance are not carried out in accordance with the instructions
and information provided in this document.
Respect the operating ranges for low pressure or high pressure
applications defined by TECUMSEH.
2

- TECHNICAL CHARACTERISTICS

■ 2.1.
Serial label for the WINTSYS® range
See annex 1 bis
■ 2.2.

Safety feature

All units are delivered with a switch-disconnector fitted with a
handle that is lockable in the ON or OFF position and a HP/LP
adjustable pressure switch with automatic (factory setting) or
manual reset. The choice of reset is made using a switch (see
annex 7). The pressure switch has a 16 A breaking capacity.
■ 2.3.

Refrigeration diagrams

See annex 2
3
- INSTALLATION
■ 3.1.

Unpacking

Before unpacking, check that the packaging has not been
damaged in any way and that the exterior is in good condition.
■ 3.2.

Handling

The packaging enables the unit to be moved using a forklift
truck or a pallet truck. It is recommended that the packaging is
kept in place until the unit reaches the installation location.
The unpacked WINTSYS® should not be dragged along the
ground.
■ 3.3.

Location

The WINTSYS® should not block or obstruct thoroughfares,
doors, shutters or the movement of personnel.
The surface supporting the unit must be solid enough to bear
the combined weight of the unit and its support.
See Table annex 1 for the unit weight
Comply with the distances between the unit and any
surrounding obstacles to ensure good air circulation.
See annex 3
|

Installation Instructions

The WINTSYS® should be installed in a well-ventilated place
with no drafts. Air should be allowed to circulate around the
condenser and under the compressor. There should be no
obstacles to the front or side of the unit, in order to avoid any
recirculation of air in the condenser.
Amongst other things, this will avoid an abnormally high
condensation temperature. The unit should be installed on
level ground. For units installed at high altitudes, the effect of
the air density should be taken into account.
■ 3.4.

Acoustics

Precautions should be taken during installation to avoid
generating unwanted noise or vibration:
- the unit should be solidly attached to a stable, rigid support,
- the piping lines should be sufficiently flexible to avoid the
transmission of vibrations.
It is sometimes recommended to separate the unit from its
support and the support from the wall or the ground, using
joints made of noise-absorbing or anti-vibration materials (not
supplied). In these cases, users should comply with the
manufacturers' recommendations for their choices and
installations. TECUMSEH is not responsible for the choice of
vibration absorbers or their absorption capacity.
■ 3.5.

Attachment

The unit should be installed and fixed on level ground.
The sealing of supports should be performed using means
suited to the type of flooring (not supplied).
- Floor mounting
Do not use wooden rafters as a mounting rail.
Use a concrete base capable of bearing the load and the
vibrations. Use pegs suited to the materials used with an
appropriate seal length.
■ 3.6.

Access to connection points

■ 3.7.

Refrigeration connections

To ensure the quality of our products, the unit's refrigeration
circuit is dry charged. It is delivered pressurized with nitrogen.
Tightening torque for valves on
the compressors and receivers
COMPRESSORS
AJ
FH
FH
RECEIVERS
0.75 L to 3.9 L
See annex 3
See annex 4
SUCTION
DISCHARGE
VALVE
VALVE
70 to 85 Nm
/
114 to 126 Nm
114 to 126 Nm
114 to 126 Nm
70 to 85 Nm
FLUID VALVES
70 to 85 Nm
366474_b / 09.2019
9/44