10.2 Assignment of error codes
In case of a fault, the error codes will be displayed on the 7 segment display on the base board.
Error code
Description
----
No voltage
U
Voltage below specification
O
Housing internal
temperature too high (>80
°C)
S
Time from end position
to end position too long (>
120s)
Voltage above specification
Heating defective and T =
< 0 °C
e
Error in position detection
P
Invalid position
E
Emergency manual override
active
9
No communication with
accessories
I
Actuator was run in motor
current limit
Further error codes can be found in the corresponding accessory user manuals
"Ready-to-operate"
signal
No
No
No
No
No
No
No
No
No
No
No
Help in case of faults
EA response
None
None
Stops
Stops
Stops
Normal
operation
None
Normal
operation
None
None
Stops
63