Herunterladen Inhalt Inhalt Diese Seite drucken

GF EA15 Bedienungsanleitung Seite 55

Vorschau ausblenden Andere Handbücher für EA15:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Instruction manual
Make sure that no water enters the actuator.
Mount the cable routing, so it does not point upwards.
Requirements
 Recommended connecting cable specifications:
AWG 18-16, min. 125°C, 1000V, cUL AWM Style 4486 , outside diameter 8-13mm
(cable glands), 4-9mm (DIN-connectors). Wire gauge 0.75...1.5 mm²
Sizing & position and marking of the fuse / circuit breaker (voltage supply side):
Req. external breakers on all live wires:
Rated Current: max. 16A,
Trip Curve: C
Standards Compliance: cUL489, CSA C22.2 No. 5.1, IEC 60947-2
Ensure that the circuit breaker is accessible to operating personal at all times!
Additionally ensure that all breakers installed are clearly marked in terms of
function, signal type and EA device name (i.e. EA supply, EA return line etc.)
Installation
55

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis