Malfunction
Input current over
high protection.
IPM module thermal
circuit is abnormal
IPM module
temperature too high
protection
PFC module
protection
DC fan motor failure
PFC module thermal
circuit is abnormal
Error
code
1. The compressor current is too large
momentary
2. The water flow is abnormal
EE13
3. Power fluctuations within a short
time
4. Wrong reactor
1. Output abnormity of IPM module
thermal circuit
EE14
2. Fan motor is abnormal or damaged
3. Fan blade is broken
1. Output exception of IPM module
thermal circuit
2. Fan motor is abnormal or damaged
EE15
3. Fan blade is broken
4.The screw on driver board is loose
1. Output exception of PFC module
2. Fan motor is abnormal or damaged
EE16
3. Fan blade is broken
4. Input voltage leap, input power is
abnormal
1. DC motor is damaged
2. For the tri-phase check if the
neutral is connected
EE17
3. Main board or fan motor driving
board is damaged
4. The fan blade is stuck
EE18
The driver board is damaged
Reason
- 22 -
Solution
1. Check the compressor if it works
normally
2. Check the waterway system
3. Check if the power is in the normal range
4. Check if the reactor is used correctly.
1. Check if the motor speed is too low or fan
motor is damaged, replace it by a new one.
2. Replace a new driver board
3. Change the fan blade if it is broken
1. Check the main board or replace the
driver board
2. Check if the motor speed is too low or fan
motor is damaged, replace it by a new one if
any failure.
3. Change the fan blade if it is broken
4. Check the screw on driver board
1.Check the main board or replace the driver
board
2. Check if the motor speed is too low or fan
motor is damaged, replace it by a new one.
3. Change the fan blade
4. Check the input voltage
1. Detect DC motor for mono phase
machine, replace a new one if any failure
2. Check the wiring connection for tri-phase
machine
3. Check the board, replace a new fan motor
driver board or main board if any failure
4. Check if there is any barrier in front of
fan blade and remove it
1. Check if the motor speed is too low or fan
motor is damaged, replace it by a new one.
2. Change a new driver board