5.4 Adjusting the bypass
Use the following procedure to adjust the bypass:
1.Valve 1 wide open. Valve 2 & valve 3 closed.
2.Slowly open valve 2 & valve 3 by half, then close the valve 1 slowly to increase the water flow to valve 2 &
valve 3.
3. If it shows 'ON' or 'EE3' on display, it means the water flow into heat pump is not enough, then you need adjust
the valves to increase the water flow through the heat pump.
How to get the optimum water flow:
Please turn on the heat pump under heating function, firstly close the by-pass then open it slowly to start the heat
pump (the machine can't start running when the water flow is insufficient).
Continue to adjust the by-pass, at the meantime to check the Inlet water temp. & Outlet water temp., it will be
optimum when the difference is around 2 degree.

6. Initial operation

Note: In order to heat the water in the pool (or hot tub), the filter pump must be running to cause the
water to circulate through the heat pump. The heat pump will not start up if the water is not
circulating.
After all connections have been made and checked, carry out the following procedure:
1) Switch on the filter pump. Check for leaks and verify that water is flowing from and to the swimming
pool.
2) Connect power to the heat pump and press the On/Off button
unit will start up after the time delay expires (see below).
3) After a few minutes, check whether the air blowing out of the unit is cooler.
4) When turn off the filter pump , the unit should also turn off automatically , if not, then adjust the flow
switch.
on the electronic control panel. The
- 10 -