Mounting
HOT PROBE TIP
The probe tip can reach temperatures of more than 100°C.
Avoid any contact with the probe tip.
Failure to follow these instructions can result in death, serious injury or
equipment damage.
When the product is switched on, the heat-up time of the PTC thermistor is
up to 15 seconds. This heat-up time must elapse before the product is ready
for operation.
When the probe is pulled out of a liquid, the heat-up time of the PTC thermis-
tor is approximately 30 seconds. This heat-up time must elapse before the
product is ready for operation.
Consider these response delays when selecting the height at which the
probe is/probes are to be mounted.
5.1
Preparing mounting
 Verify that the product is mounted to an even, rigid and dry wall at eye
level.
 Verify that the permissible ambient temperature is respected at the prod-
uct.
 Verify that the product is accessible and easy to oversee at all times.
 Verify that the product is protected against water and splash water.
Mounting
WARNING
RG 210
EN
18