2. SELECTING THE INSTALLATION SITE

2-1. Indoor Unit

AVOID:
● areas where leakage of flammable gas may be expected.
● locations where sulfurous acid gas or corrosive gas occurs.
● places where large amounts of oil mist exist such a kitchen
of a Chinese restaurant or near a machinery equipment of
the factory. The oil can be adhered to the surface of the
heat exchanger or resin parts and this will cause a decrease
in performance, spray or drip water and deformation or
damages.
● direct sunlight.
● locations near heat sources which may affect the
performance of the unit.
● locations where external air may enter the room directly.
This may cause "condensation" on the air discharge ports,
causing them to spray or drip water.
● locations where the remote controller will be splashed with
water or affected by dampness or humidity.
● installing the remote controller behind curtains or furniture.
● locations where high-frequency emissions are generated.
● turning ON the power or operate the unit until work of
refrigerant tubing and electrical wiring have been completed.
Highly dangerous electrical voltages are used in this system.
DO:
● Install the unit to allow cool air (and warm air) to flow
smoothly. Never place objects near the air inlet or the air
outlet of the unit. This will reduce the efficiency of the unit.
● select an installation location which is rigid and strong
enough to support or hold the unit.
● select a location which can support a load that is four times
the indoor unit weight.
● select a location for drainage work properly.
If it is improperly, this will cause damage to property.
• Select a location where tubing and drain pipe have the
shortest run to the outdoor unit.
• Insulate the drain pipe running inside the building.
• Pay attention to the drainage planning not to cause
neighbors trouble.
● allow room for operation and maintenance as well as
unrestricted air flow around the unit.
● keep the fire alarm and the air outlet at least 1.5 m away
from the unit.
● recommended installation height for indoor unit shall be at
least 2.5 m.
● when installing the unit in the hotel rooms or executive
offices with a low-level noise, it is recommended that the
external electronic expansion valve kit (optional) be installed.
● the limitation of the tubing length between the indoor and
the outdoor units should be referred to the Installation
Instructions of the outdoor unit.
● allow room for mounting the remote controller about 1 m off
the floor, in an area that is not in direct sunlight or in the flow
of cool air from the indoor unit.
NOTE
Air delivery will be degraded if the distance from the floor to the
ceiling is greater than 3 m.
The air inlet and outlet of the indoor unit must be free of any
obstructions to allow air to spread throughout the room.
1.
The indoor unit must be within a maintenance space.
Over
50 mm
Over 2.5 m
(Recommended)
8

Wall Mounted

Over 75 mm
Over
50 mm
Front View
Over
Obstacles
60 mm
100 mm or less