The use of smoke alarm devices is gov-
erned by DIN 14676.
Minimum equipment
Bedrooms
•
Children's bedroom
•
Guest room
•
Corridors that serve as escape routes
•
Stairwells of apartment buildings
•
Optimal equipment
All residential and hobby rooms
•
Heating and work spaces
•
Office or workroom
•
Cellar
•
Attic
•
Conditional equipment
In kitchens, smoke alarm devices must
•
only be installed when false alarms
(e.g., caused by steam) are excluded
Not recommended
Bathrooms are excluded from the in-
•
stallation of smoke alarm devices due
to the high development of steam
42
Downloaded from
www.Manualslib.com
Operating Manual: PX-1 - Smoke Alarm Device
manuals search engine
Exception: bathrooms with
•
washing machines and cabinets
4.1 Area to be monitored
Use a device if at least one of the follow-
ing applies:
Monitoring area less than 60 m
•
and ceiling height of less than 6 m
Ceiling panels (height lower than
•
20 cm) with joists (ceiling surface
less than 36 m
Use additional equipment if at least one
of the following applies:
Monitoring area greater than 60 m
•
Ceiling height greater than 6 m
•
High partial walls
•
Separating pieces of furniture
•
Platform / gallery (area greater than
•
16 m², at least 2 m long and wide)
Ceiling panels (height greater than
•
20 cm) with joists (ceiling surface
more than 36 m
,
2
)
2
)
2
2