7.3. Switching the upper limit of cooling
temperature
This setting can be raised the upper limit of the cooling temperature setting range.
This setting can be used when connecting to the following controllers.
• Wired remote controller (2-wire type)
• Central remote controller
• Touch panel controller
• System controller
• Service tool
• Web monitoring tool

DIP switch setting

Set the DIP switch SET 4 SW3 referring to the Table C.
Table C
DIP switch SET 4 SW3
OFF (Factory setting)
NOTE :
Please do not make a standard setup and an extension setup intermingled in remote
controller group.

7.4. Function setting

• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
(Set IU AD, REF AD SW to 0)
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air
tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
number
Filter
indicator
11
interval
Filter
indicator
13
action
Cool air
tem-
30
perature
trigger
Heat air
tem-
31
perature
trigger
En-13
9373870111-01_IM.indb Sec1:13
9373870111-01_IM.indb Sec1:13
Downloaded from
www.Manualslib.com
ON
DIP switch "SET4"
OFF
SW
SW
SW
SW
1
2
3
4
Cooling temperature setting range
Standard (18 to 30 °C)
ON
Extension (18 to 32 °C)
Setting number
Default
00
Default
Adjust the fi lter cleaning interval
notifi cation. If the notifi cation is too
01
Longer
early, change to setting 01. If the
notifi cation is too late, change to
02
Shorter
setting 02.
00
Enable
01
Disable
Enable or disable the fi lter indicator.
Display
Setting 02 is for use with a central
only on
remote controller.
02
central
remote
controller
00
Default
Adjust the cool air trigger
temperature. To lower the trigger
01
Adjust (1)
temperature, use setting 01. To
raise the trigger temperature, use
02
Adjust (2)
setting 02.
00
Default
Adjust the heat air trigger
temperature. To lower the trigger
01
Adjust (1)
temperature by 6 degrees C, use
setting 01. To lower the trigger
02
Adjust (2)
temperature by 4 degrees C, use
setting 02. To raise the trigger
03
Adjust (3)
temperature, use setting 03.
manuals search engine
Auto
40
restart
Cool Air
Preven-
43
tion
External
46
control
Error re-
47
port target
Fan set-
ting when
cooling
49
thermostat
OFF

8. TEST RUN

] 1

8.1. Test run using Outdoor unit (PCB)

• Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to
be used for the test run.

8.2. Test run using remote controller

• Refer to the Installation Manual for the remote controller to perform the test run using
the remote controller.
• When the air conditioner is being test run, the OPERATION and TIMER indicator lamps
fl ash slowly at the same time.
For details, please refer to the Manual of "IR Receiver Unit" or "Wired Remote Controller".

9. CHECK LIST

Pay special attention to the check items below when installing the indoor unit(s). After
] 1
installation is complete, be sure to check the following check items again.
Check items
Has the indoor unit been installed cor-
rectly?
Details
Has there been a check for gas leaks
(refrigerant pipes)?
Has heat insulation work been com-
pleted?
Does water drain easily from the
indoor units?
Is the voltage of the power source the
same as that indicated on the label on
the indoor unit?
Are the wires and pipes all connected
completely?
Is the indoor unit earthed (grounded)?
Is the connection cable the specifi ed
thickness?
Are the inlets and outlets free of any
obstacles?
Does start and stop air conditioner
operation by remote controller or
external device?
After installation is completed, has the
proper operation and handling been
explained to the user?
sdasdsadxxxx
00
Enable
Enable or disable automatic system
restart after a power outage.
01
Disable
00
Super low
Restrain the cold airfl ow with mak-
Follow the
ing the airfl ow lower when starting
setting on
heating operation. To correspond to
01
the remote
the ventilation, set to 01.
controller
Allow an external controller to start
00
Start/Stop
or stop the system, or to perform
an emergency stop.
* If an emergency stop is performed
from an external controller,
Emergen-
01
all refrigerant systems will be
cy stop
disabled.
* If forced stop is set, indoor unit
stops by the input to the external
Forced
02
input terminals, and Start/Stop by
stop
a remote controller is restricted.
00
All
Change the target for reporting er-
Display
rors. Errors can either be reported
only on
in all locations, or only on the wired
01
central
remote.
remote
controller
Follow the
When set to 01, the fan stops when
setting on
the thermostat is OFF in cooling
00
the remote
operation. Connection of the wired
controller
remote controller (2-wire type
or 3-wire type) and switching its
01
Stop
thermistor are necessary.
If not performed correctly
Vibration, noise, indoor unit may drop
No cooling, No heating
Water leakage
Water leakage
No operation, heat or burn damage
No operation, heat or burn damage
Short circuit
No operation, heat or burn damage
No cooling, No heating
No operation
Check
box