Herunterladen Inhalt Inhalt Diese Seite drucken

SFA Sanicondens Clim Mini S Bedienungs- & Installationsanleitung Seite 8

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 9
EN
Disconnect the electrical supply
before carrying out work on the unit!
1. Safety
- Designed only for pumping water.
- Must not run dry.
- Do not submerge.
2. Box contents
Sanicondens® Clim Mini comprises two components : a pump unit and a
triple-level sensor.
1: pump
2: level sensor
2a: lid
2b: float ball
2c: filter
2d: reservoir
2e: stopper
3: rubber elbow
4: pipe 1.2m, Øint 4.6mm
5: vent connection.
6: cable with coupler
7: support bracket
8: Vent valve
3. Technical data
Sound level at 1 m
21 dB
Max. flow rate
9 L/h +/- 15%
Max. horizontal
20 m
discharge (50 Hz)
Maximum vertical
6 m
discharge (50 Hz)
Maximum priming head
2 m
220-240 V~
Electricity supply
50-60 Hz
Power
22 W
Trips at 130°C and
Thermal protection
then automatically
resets
Maximum temperature
35°C
of water
4. Installation
Install indoors only (domestic or industrial
premises).
4.1 Level Sensor unit
- Magnet facing
upwards.
- Cover on.
- Connect the short pipe
(150mm) to the lid vent,
point it upwards and secure.
- Fit the level sensor horizontally
using the support supplied.
4.2 Pump unit
- Install the pump in the trunking (1) or in the suspended ceiling (2).
- Make sure the the pump is pointing in the right direction (see arrows
on the pump unit).
- Install the pump vertically (preferably).
- Make sure there is enough room around the pump unit for it to cool off
in the event of prolonged usage.
- Ensure that electrical connections are not exposed to water.
8
Height (m)
25
20
15
10
5
0
0
1
2
3
4
5
6
7
Flow rate (L/h)
4.3 Hydraulic connections
- Feed the incoming condensate to the level sensor inlet (1).
- Connect the pump and the level sensor up using the pipe supplied (2).
- Evacuation (3):
The pump outlet must be connected to the waste water discharge using
a suitable fitting with an inner diameter of 6 mm (not supplied).
Warning: To prevent siphoning, the discharge outlet must be
!
higher than the condensate tank.
If the discharge hose runs below the pump level, place the supplied vent
valve (#8) on the discharge hose at the highest point in the circuit.
4.4 Electric connections
- Connect the level sensor to the pump unit using the
cable.
- To connect the alarm, there are
(normally open/ normally
8
9
10
closed) contacts,
recommended interrupting
capacity = 2A (5Maxi).
Connect the alarm as shown in
the wiring
setup diagram.
- Electricity supply:
Plug the pump in (phase, earth, neutral):
• either by way of the air conditioner,
• or directly using a 30-mA circuit breaker.
5. Start-up
- Check pumping direction.
- Introduce water into the level sensor.
- Check that the pump starts up and then stops once the water level has
dropped.
- Check that the connections are all waterproof.
6. Maintenance
- Maintenance must only be carried out with the appliance switched off.
- This product must be maintained at the start of each summer season,
or regularly if the pump is used year round.
- Clean:
• the reservoir,
• the filter,
• the float ball.
Replace all items and close the reservoir.
7. Guarantee
Sanicondens® Clim Mini is guaranteed for two years subject to correct
installation and usage.
White
NC
NO
Black
Purple

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis