16
Mounting and Connection Instructions 2 Detector group module
6.
Programming
The DIP switches are only queried during initialization (when the operating voltage is
applied). Therefore, the setting of this switch is only effective when energized!
6.1
Select BUS system
ON
S1/8
OFF
6.2
Select module type at BUS-2
ON
S1/7
OFF
6.3
Select module type at BUS-1
The desired type of module (1 DG- or Universal
connection module) is selected in the control
panel programming.
Operation as Detector Group Module:
ON
S1/7
OFF
6.4
BUS user address
6.4.1
Address setting
The DIP switches S1/1 to S1/6 serve as coding for the
BUS-2 and BUS-1 user address. The illustration shows
the position and valence of the switches.
In the event of several users, each user must be assigned
its own address.
Permissible address range: 1 to 62 or 63 (see below).
6.4.2
Address allocation at BUS-1
-
Operation as 1 Detector group module:
(highest address 63).
-
Operation as 2 Detector group module:
(highest address 62).
Only the first address is set at the module. The module occupies the subsequent address
automatically.
The highest settable address is 62, otherwise the permissible address range is exceeded by the
automatically assigned address.
Ensure that the automatically assigned address is not already occupied by an other user.
6.4.3
Address allocation at BUS-2
The module only occupies the set address (highest address 63).
Operation at BUS-2
Operation at BUS-1
Operation as DUO I/O Module
Operation as 5 Input module
Operation as 1 DG Module
Operation as 2 DG Module
BUS-2
see 6.2/6.3
Address
BUS-2
BUS-1
The module occupies 1 address
The module occupies 2 addresses
BUS-2/BUS-1, f.m.
8
S1
1
S1
BUS-1
see 6.2/6.3
32
16
8
Valence
4
2
1
ON