Installation and Operating Instructions
Service menu | 09 – Temperature sensor
05 -
Filter calibration
08 -
AQS Sensor
Temperature sensor
10 -
Supply Duct Limits
Bypass Temperature
11 -
Temperature sensor
Supply duct:
Temperature sensor for the supply air in the building.
Extract duct:
Temperature sensor for the extract air in the building.
Room:
The temperature sensor (option) installed in the measurement area (option).
Room BMS:
Setpoint temperature via Modbus or BACnet.
Service menu | 10 – Supply Duct Limits
08 -
AQS Sensor
09 -
Temperature sensor
Supply Duct Limits
11 -
Bypass Temperature
12 -
Flow Offset
Supply Duct Limits
Maximum
temp. Supply air
duct
Minimum
temp. Supply air
duct
It is recommended to keep the flow rate reduction activated.
If the sensor in the supply air duct is selected, a maximum temperature
cannot be set at the same time.
Decentralised ventilation unit – KWL
Temperature sen-
Supply duct
sor set value
Extract duct
to set the unit
Room
Room BMS
Flow reduction
Activate or deacti-
under min.
vate the unit
output reduction if
the minimum
temperature is not
reached
(activated as
standard)
®
Yoga / KWL
Service menu | 11 – Bypass Temperature
09 -
10 -
12 -
13 -
Bypass Temperature
Odtok 0 %
Minimum intake air temperature at which bypass can be opened.
Range 0 to 20 °C.
Service menu | 12 – Supply air flow deviation
10 -
11 -
13 -
14 -
Air flow deviation
0 % equal pressure
+ values – overpress.
- values – underpre.
26
®
Yoga Style
Temperature sensor
Supply Duct Limits
Bypass Temperature
Flow Offset
Fire Flow
Supply Duct Limits
Bypass Temperature
Flow Offset
Fire Flow
Occupancy
Flow Offset
Flow 0%

Quicklinks ausblenden: