Herunterladen Inhalt Inhalt Diese Seite drucken

Overview Sounder/Flasher; Structure Of Device; Tear-Off Contact; Pull Relief - Honeywell 2MG BUS-2 Montage, Anschluss, Anleitung

Signalgeber
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

12
3.

Overview Sounder/Flasher

3.1

Structure of device

Cover contact
Alarm device
3.2

Tear-off contact

Screw the tear-off contact (eye with lead) directly to the mounting surface using the enclosed screw
and spacer sleeve. Details see chapter 9. "Mounting Tear-off contact".
3.3

Pull relief

Use a cable binder to attach the connecting cables to the pull relief.
4.

Function

4.1

Detector group inputs

(Function only
- The 2 detector groups operate with a stabilized voltage of 3.3 V DC.
- End of line resistor programmable: fixed value 12k1 or 10k, freely programmable 4k to 14k
(depending on monitoring area)
- Monitoring area programmable: ±20%, ±30% or ±40%
The states of the 2 detector groups are transmitted separately in the bus protocol via
Triggering of a cover contact
protocol.
4.2
Acoustical / optical alarm signalling
The module provides an optical alarm device with two high-performance LEDs and an acoustical
alarm device with piezo signalling device. Optical and acoustical alarm can be activatet separately.
The function depends on control panel programming.
Optical alarm (Impulse, static on, brightness) and acoustical alarm (Intervall, static on, loudness)
can be set up.
Mounting and Connection Instructions Sounder/Flasher with 2 Inputs BUS-2
Fixing hole
in conjunction with
is signalled separately as tamper to the control panel in the bus
Fixing hole
LEDs
ON
1 2 3 4 5 6
MB-Secure, see 5.1)
Pull relief
Cable entry
Tear-off contact
one address.

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis