Appendix
12. Appendix
12.1 FAQs
QUESTION
Is it possible to connect two
heating circuits to one "Uni-
box T-RTL vario"?
How many m² of temperature
regulation surface can be
connected to the "Unibox
T-RTL vario"?
36
RESPONSE
Yes, use a"Duo connection piece" to connect two heating
circuits of the same length to one "Unibox T-RTL vario". Each
surface temperature regulation circuit may have a maximum
pipe length of 80 m, provided you use 16/17 mm pipes.
Illust. 12: Connection scheme of two heating circuits with "Duo
connection piece"
You can connect a surface covering approximately 20 m² per
"Unibox T-RTL vario". The pipe length must not exceed 100 m
when using a 17 mm pipe.
Unibox T-RTL vario
102273480-V03.06.2020