PARAMETER SETTINGS
– switch the thermostat off with the "
– To go to the menu, press the "M" and "+" buttons simultaneously for 1 0 sec. until " " appears. Adjust the settings with the "+" or "-" buttons.
– scroll through the menu with the "M" button.
MENU
DESCRIPTION
Temp. Offset
01
Maximum temperature
03
Minimum temperature
04
Display mode
05
Dead Band
06
Frost protection
07
Sensor selection
09
Reboot memory
10
2-pipes/4-pipes select
11
(0-1 0V) select dead band or not
12
Mode
13
Fanspeed
14
Maximum fan speed
15
Medium fan speed
16
Low fan speed
17
Factory reset
18
10D7 Software version
" button
ADJUSTABLE
-8°C ... +8°C (+0,5°C)
+1 0 °C ... +40°C (+0,5°C)
+1 0 °C ... +40°C (+0,5°C)
Room / Set / Room set
0°C ... +3°C (+0,5°C)
+1 0 °C ... +20°C (+0,5°C)
NO / NC
'0': do not save / '1 ': save
'2': 2-pipe connection / '4': 4-pipe connection
'0': With dead band / '1 ': Without dead band
Heating / Cooling / Heating + Cooling / Auto select (enkel 4-pijps)
80% - 90% - 1 00% / Auto mode
80% ... 1 00%
45% ... 75%
20% ... 40%
'0': not back to factory settings / '1 ': Factory reset
After selecting "1 ", press the "
was successful.
1 0D7 - Version 27
" button to go to the startup window. Recovery