Removing the Grille
Insert a small tool (no larger than 1.5 millimeters in diameter) through the grille perforation at the edge of the grille and pull to disengage
the grille.
CAUTION: Do not use a screwdriver to pry the grille from the enclosure. This could result in damage to the loudspeaker.

Safety and Regulatory Compliance

The Bose FreeSpace FS2P loudspeaker has passed testing and complies with the following specifications and uses:
Listed to ANSI/UL 1480-2016, CAN/ULC-S541
Fire Protective Signaling Use – UL Category UUMW/UUMW7, File Number S 3241. Control Number 42S9.
Not for use with DC-supervised systems.
Suitable for use indoors in dry locations.
EN 54-24: 2008, Loudspeaker for Voice Alarm Systems for Fire Detection and Fire Alarm Systems for Buildings
Environmental: Type A (indoor applications)
Suitable for installation using Class 1, Class 2, or Class 3 wiring methods in accordance with NFPA 70, National Electric Code, 2002, Article 640.
Suitable for use with fire alarm circuit wiring methods in accordance with NFPA 70, National Electric Code, 2002, Article 760.
NFPA 70, National Electric Code, 2002, Article 300-22 (c).
NFPA 90-A, 2002, Installation of Air Conditioning and Ventilation Systems, Paragraph 4.3.10.2.6.5.
EMC Directive 89/336/EEC and Article 10 (1) of the directive, EN50081-1 and EN50082-1 as signified by the CE mark.
The FreeSpace FS2P loudspeaker has been designed to the requirements defined in the following European regulatory specification for combination
systems:
British Standard Code of Practice BS 5839, Part 8, when used with the ceramic terminal block and thermal fuse.
Tested to IEC60268-5.
Nominal Coverage Angle (per UL 1480) Vertical: 120°/60° at –3 dB; 150°/30° at –6 dB
UL Sensitivity Wattage Tap Sound Pressure Level dBA at 3.1 meters (10 feet):
Wattage
CAN/ULC-S541
Canada
Tap
70 V
100 V
1 W
78.0 dBA
2 W
80.3 dBA
80.1 dBA
4 W
82.9 dBA
82.6 dBA
8 W
85.4 dBA
85.2 dBA
16 W
87.2 dBA
87.1 dBA
16 Ω
86.7 dBA
SPLs given are per the UL 1480 specified reporting method.
Frequency response:
Fire alarm (UL): 95 Hz to 17000 Hz
Installation Guide • FreeSpace FS2P
Horizontal: 110°/70° at –3 dB; 140°/40° at –6 dB
Wattage
ANSI/UL 1480-2016
United States
Tap
70 V
1 W
72.4 dBA
2 W
75.1 dBA
4 W
77.8 dBA
8 W
80.4 dBA
16 W
82.7 dBA
16 Ω
83.0 dBA
100 V
75.0 dBA
77.6 dBA
80.1 dBA
82.6 dBA
100 The Mountain Rd, Framingham, MA 01701
Loudspeaker for voice alarm systems for fire detection and fire
For DOP 434849-2, see pro.Bose.com/FS2PDOP
Installation
0843
Bose Corporation
20
DOP 434849-2
EN 54-24: 2008
alarm systems for buildings